Cold-shrinkable cable termination kit & straight joint kit
0.6/1KV-Cold Shrinkable Cable Accessories
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
0.6/1kV 3-cores Cold Shrinkable Termination Kits | VLZ-1/3.0 | 10~16 | 0.6/1kV 3-cores Cold Shrinkable Joint | VLJ-1/3.0 | 10~16 |
VLZ-1/3.1 | 25~50 | VLJ-1/3.1 | 25~50 | ||
VLZ-1/3.2 | 70~120 | VLJ-1/3.2 | 70~120 | ||
VLZ-1/3.3 | 150~240 | VLJ-1/3.3 | 150~240 | ||
VLZ-1/3.4 | 300~400 | VLJ-1/3.4 | 300~400 | ||
0.6/1kV 4-cores Cold Shrinkable Termination Kits | VLZ-1/4.0 | 10~16 | 0.6/1kV 4-cores Cold Shrinkable Joint | VLJ-1/4.0 | 10~16 |
VLZ-1/4.1 | 25~50 | VLJ-1/4.1 | 25~50 | ||
VLZ-1/4.2 | 70~120 | VLJ-1/4.2 | 70~120 | ||
VLZ-1/4.3 | 150~240 | VLJ-1/4.3 | 150~240 | ||
VLZ-1/4.4 | 300~400 | VLJ-1/4.4 | 300~400 | ||
0.6/1kV 5-cores Cold Shrinkable Termination Kits | VLZ-1/5.0 | 10~16 | 0.6/1kV 5-cores Cold Shrinkable Joint | VLJ-1/5.0 | 10~16 |
VLZ-1/5.1 | 25~50 | VLJ-1/5.1 | 25~50 | ||
VLZ-1/5.2 | 70~120 | VLJ-1/5.2 | 70~120 | ||
VLZ-1/5.3 | 150~240 | VLJ-1/5.3 | 150~240 | ||
VLZ-1/5.4 | 300~400 | VLJ-1/5.4 | 300~400 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage Test | 4kV/1min,No breakdown no flashover | Pass,meet the requirements | |||
Power Frequency Voltage Test | 2.4kV/4 hours,No breakdown no flashover | Pass,meet the requirements |
8.7/15KV-Cold Shrinkable Cable Accessories
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
8.7/15kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-10/1.1 | 25~50 |
VLN-10/3.2 | 70~120 | VLN-10/1.2 | 70~120 | ||
VLN-10/3.3 | 150~240 | VLN-10/1.3 | 150~240 | ||
VLN-10/3.4 | 300~400 | VLN-10/1.4 | 300~400 | ||
VLN-10/3.5 | 500~630 | VLN-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-10/1.1 | 25~50 |
VLW-10/3.2 | 70~120 | VLW-10/1.2 | 70~120 | ||
VLW-10/3.3 | 150~240 | VLW-10/1.3 | 150~240 | ||
VLW-10/3.4 | 300~400 | VLW-10/1.4 | 300~400 | ||
VLW-10/3.5 | 500~630 | VLW-10/1.5 | 500~630 | ||
8.7/15kV 3-cores Cold Shrinkable Joint | VLJ-10/3.1 | 25~50 | 8.7/15kV Single Core Cold Shrinkable Joint | VLJ-10/1.1 | 25~50 |
VLJ-10/3.2 | 70~120 | VLJ-10/1.2 | 70~120 | ||
VLJ-10/3.3 | 150~240 | VLJ-10/1.3 | 150~240 | ||
VLJ-10/3.4 | 300~400 | VLJ-10/1.4 | 300~400 | ||
VLJ-10/3.5 | 500~630 | VLJ-10/1.5 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 39kV 5min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 15kV, Discharge volume≤10pc | Pass | |||
Impulse Voltage Test | Under 95kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 23kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC) | Under 15kV, Discharge volume≤10pc | Pass | |||
Constant load Cycle Test | The conductor applied voltage 23kV, and heated to (95-100ºC). In which the temperature stability 2h, cooling 3h, a total of 60 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC,and at ambient temperature) | Under 15kV, Discharge volume≤10pc | Pass | |||
Thermal Stability Test | Under 23 KA, Short circuit 2 times, No visible damage | Pass | |||
Dynamic Stability Test | Under 81 KA, Short circuit 1 time, No visible damage | Pass | |||
Impulse Voltage Test | 95kV, ±10 times | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 23kV, 15min | Not Flashover and Not Breakdown | |||
Tide Temperature Test | 11kV, 300h | Not Flashover,Not Breakdown and No Overcurrent Release | |||
Salt Spray Test | 11kV, 1000h | Not Flashover,Not Breakdown and No Overcurrent Release |
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
18/20kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-10/1.1 | 35~70 |
VLN-20/3.2 | 95~185 | VLN-10/1.2 | 95~185 | ||
VLN-20/3.3 | 240~400 | VLN-10/1.3 | 240~400 | ||
VLN-20/3.4 | 500~630 | VLN-10/1.4 | 500~630 | ||
18/20kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-10/1.1 | 35~70 |
VLW-20/3.2 | 95~185 | VLW-10/1.2 | 95~185 | ||
VLW-20/3.3 | 240~400 | VLW-10/1.3 | 240~400 | ||
VLW-20/3.4 | 500~630 | VLW-10/1.4 | 500~630 | ||
18/20kV 3-cores Cold Shrinkable Joint | VLJ-20/3.1 | 35~70 | 18/20kV Single Core Cold Shrinkable Joint | VLJ-10/1.1 | 35~70 |
VLJ-20/3.2 | 95~185 | VLJ-10/1.2 | 95~185 | ||
VLJ-20/3.3 | 240~400 | VLJ-10/1.3 | 240~400 | ||
VLJ-20/3.4 | 500~630 | VLJ-10/1.4 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 54kV 5min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 20kV, Discharge volume≤10pc | Pass | |||
Impulse Voltage Test | Under 125kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 35kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC) | Under 20kV, Discharge volume≤10pc | Pass | |||
Constant load Cycle Test | The conductor applied voltage 35kV, and heated to (95-100ºC). In which the temperature stability 2h, cooling 3h, a total of 60 cycles | Not Flashover and assessed by the following test results | |||
Partial Discharge (the normal operation of the high temperature and conductor 5-10ºC,and at ambient temperature) | Under 20kV, Discharge volume≤10pc | Pass | |||
Thermal Stability Test | Under 23 KA, Short circuit 2 times, No visible damage | Pass | |||
Dynamic Stability Test | Under 81 KA, Short circuit 1 time, No visible damage | Pass | |||
Impulse Voltage Test | 125kV, ±10 times | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 30kV, 15min | Not Flashover and Not Breakdown | |||
Tide Temperature Test | 15kV, 300h | Not Flashover,Not Breakdown and No Overcurrent Release | |||
Salt Spray Test | 15kV, 1000h | Not Flashover,Not Breakdown and No Overcurrent Release |
Name | Item No. | Suit cables’ sectional area (sqmm) | Name | Item No. | Suit cables’ sectional area (sqmm) |
26/35kV 3-cores Cold Shrinkable Indoor Termination Kits | VLN-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Indoor Termination Kits | VLN-35/1.1 | 35~70 |
VLN-35/3.2 | 120~185 | VLN-35/1.2 | 95~185 | ||
VLN-35/3.3 | 240~400 | VLN-35/1.3 | 240~400 | ||
VLN-35/3.4 | 500~630 | VLN-35/1.4 | 500~630 | ||
26/35kV 3-cores Cold Shrinkable Outdoor Termination Kits | VLW-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Outdoor Termination Kits | VLW-35/1.1 | 35~70 |
VLW-35/3.2 | 120~185 | VLW-35/1.2 | 95~185 | ||
VLW-35/3.3 | 240~400 | VLW-35/1.3 | 240~400 | ||
VLW-35/3.4 | 500~630 | VLW-35/1.4 | 500~630 | ||
26/35kV 3-cores Cold Shrinkable Joint | VLJ-35/3.1 | 50~95 | 26/35kV Single Core Cold Shrinkable Joint | VLJ-35/1.1 | 35~70 |
VLJ-35/3.2 | 120~185 | VLJ-35/1.2 | 95~185 | ||
VLJ-35/3.3 | 240~400 | VLJ-35/1.3 | 240~400 | ||
VLJ-35/3.4 | 500~630 | VLJ-35/1.4 | 500~630 |
Test Project | Standard Requirements | Test Result/Conclusion | |||
Power Frequency Voltage | 105kV 1min Not Flashover and Not Breakdown | Pass | |||
Partial Discharge | Under 39kV, Discharge volume≤10pc | Pass | |||
Constant Voltage load Cycle (in air) | The conductor applied voltage 23kV,and heated to (95-100ºC). In which the temperature stability 2h,cooling 3h, a total of 3 cycles | Not Flashover and assessed by the following test results | |||
Impulse Voltage Test | Under 250kV, ±10 times,No breakdown no flashover | Not Flashover and Not Breakdown | |||
DC Voltage | 156kV, 15min | Not Flashover and Not Breakdown | |||
AC Withstand Voltage | 104kV, 4h | Not Flashover and Not Breakdown |
View more products,you can click photos…
66~500kV High Voltage Cable Accessories 1~35kV Heat Shrink Cable Accessories Grounding Box
Customized Silicone Rubber Protector Heat Shrinkable Tubing Explosion Proof Box
/* January 22, 2024 19:08:37 */!function(){function s(e,r){var a,o={};try{e&&e.split(«,»).forEach(function(e,t){e&&(a=e.match(/(.*?):(.*)$/))&&1
Кто мы Китай 35kv кабельные аксессуары 3-жильный термоусадочная кабельная заделка производитель и поставщик,Вы можете получить более подробную информацию по электронной почте, вы получите дешевую или заводскую цену.
Get Latest Price Request a quote
Popular 35kv кабельные аксессуары 3-жильный термоусадочная кабельная заделка Продукты
Popular jiuweielectric Продукты
Коробка кабельных разъемов, красный защитный контейнер для кабельных соединений
Vfsm-5 φ 35/16-83 Термоусадочные колпачки для торцевых уплотнений
Комплекты разъемов для прочных соединений кабелей XLPE с низким напряжением
Клейкая лента для электромастики, изготовимая на заказ, водонепроницаемая клейкая лента
Popular комплект для оконечной нагрузки внутри помещений Продукты
Высококачественный комплект одножильной оконечной нагрузки для наружного кабеля 35 кВ
Наружный 10 кв 3 жил Холодный термоусадочный кабель прямой стык
Принадлежности для кабелей Комплект прямого термоусадочных соединений 10кв для установки в помещении
комплект 3-жильных разъемов для термоусадочных кабелей 10 кв, прямой соединитель Комплект
Комплекты термоусадочных разъемов для установки на заводе-изготовителе 1~35kv
Принадлежности для кабелей Поставщик высоковольтный термоусадочная наружная оконечная установка
Popular Комплект термоусадочных соединений Продукты
10-35kv Прямоусадочные соединения для холодной термоусадки Аксессуары для кабелей
Силиконовые резиновые соединения для установки внутри и вне помещений 10 кВ
9 в, прямой через кабельные соединения для 1 или 3 сердечников Кабели
Принадлежности для кабелей Комплект прямого термоусадочных соединений 10кв для установки в помещении
Черный / красный / серый Термоусаживаемый кабель Соединения
Tags: 35kv кабельные аксессуары 3-жильный термоусадочная кабельная заделка, jiuweielectric, комплект для оконечной нагрузки внутри помещений, Комплект термоусадочных соединений